Electrical Safety · BEEZB / BEEZZ · Topic 10 of 12
Safe work & laboratory rules
Make the workplace safe before work begins.
Key ideas
Five rules, in order
1 Disconnect completely. 2 Secure against reconnection. 3 Verify dead. 4 Earth and short-circuit. 5 Protect against adjacent live parts. The responsible person checks these measures before permission to start.
The written B command
The textbook’s ČSN 34 3100 procedure uses a written B command for work preparation, except simple and often repeated work. It records workplace, time, type of work, network/switchgear state and responsible names and signatures.
Stored energy after switching off
Switching off a circuit does not prove that stored energy is gone. Where residual voltage presents danger, use suitable discharge equipment; verify dead before work. Automatically protected test stations reduce residual voltages before live parts can be touched.
Laboratory K13114: before and during work
Enter under teacher supervision and learn the equipment first. Obtain permission before electrical operations; only the teacher switches the control panel ON. Move/connect/disconnect equipment only without applied voltage. Metal chains, rings, shorts and short sleeves are forbidden by these lab rules.
Danger, illness and leaving
In danger, students must switch the panel OFF with the big red button. Stay at your workstation; approaching rotating parts needs permission. Report illness or fatigue before work. Leave only after restoring the workstation and obtaining the teacher’s permission.
In one line: An oral message is not the written B command.
Sources
Written by Ucenly. Based on the BEEZB / BEEZZ course materials:
- bezpecnost_en, p. 87, 88, 95
- BEEZ_lecture_slides, p. 50, 51