Electrical Safety · BEEZB / BEEZZ · Topic 9 of 12
Equipment classes & IP
Distinguish shock protection from enclosure protection.
Key ideas
Class 0 and Class I
Class 0 has basic insulation without a protective-conductor connection; slide 29 states its use is prohibited in the Czech Republic. Class I combines basic insulation, protective bonding and automatic disconnection in the installation.
Class II and Class III symbols
Class II: double or reinforced insulation, no provision for PE, nested-square symbol. Class III: designed for SELV, III in a diamond. The class table uses a circled earth symbol for Class I; Class 0 has no symbol.
IP first digit: access and solids
First digit 0: no protection; 1: ≥50 mm; 2: ≥12.5 mm; 3: ≥2.5 mm; 4: ≥1 mm; 5: dust-protected; 6: dust-tight. IP2X also provides finger-access protection; X means the digit is unspecified.
IP second digit: water
0 none; 1 vertical drops; 2 drops with enclosure tilted up to 15°; 3 spraying; 4 splashing; 5 jets; 6 powerful jets; 7 temporary immersion; 8 continuous immersion under agreed conditions.
Worked examples: IP23 and IP68
IP23 combines finger/12.5 mm solid protection with spraying-water protection. IP68 combines dust-tightness with continuous immersion under manufacturer/user conditions. An immersion rating alone does not imply a water-jet rating. The code may also carry optional additional letters (A, B, C, D) and supplementary letters (H, M, S, W).
In one line: Dust-protected (5) is different from dust-tight (6).
Sources
Written by Ucenly. Based on the BEEZB / BEEZZ course materials:
- BEEZ_lecture_slides, p. 29, 31, 32
- bezpecnost_en, p. 52, 53, 54