Electrical Safety · BEEZB / BEEZZ · Topic 3 of 12

Voltage categories

Keep AC, DC and protection conditions separate.

Open the interactive lesson

Key ideas

Extra-low voltage • ELV

Slide 10 places the upper ELV boundary at 50 V AC and 120 V DC. The AC and DC columns have different limits; do not transfer a value from one column to the other.

Low voltage • LV

In the lecture diagram, LV extends above the ELV boundary to 1,000 V AC or 1,500 V DC. A 230 V AC supply is therefore low voltage in this classification. “Low” does not mean safe to touch.

High voltage • HV

The HV region begins above 1,000 V AC or above 1,500 V DC in slide 10. Always identify the current type before choosing the category.

SELV is a protection system

SELV means safety extra-low voltage. Slide 10 marks 25 V AC / 60 V DC as its basic teaching values. Slide 27 refines these by contact and environment: protected-enclosure contact permits 50 / 120 V in usual or wet conditions. Do not turn 25 / 60 into a universal definition.

Read the SELV circuit

The lecture’s SELV diagram shows a transformer separating the supply from the extra-low-voltage output. Its secondary is not connected to the source PEN. The voltage limit is one part of the protective arrangement, not the whole arrangement.

In one line: 230 V mains is LV, not ELV.