Electrical Safety · BEEZB / BEEZZ · Topic 3 of 12
Voltage categories
Keep AC, DC and protection conditions separate.
Key ideas
Extra-low voltage • ELV
Slide 10 places the upper ELV boundary at 50 V AC and 120 V DC. The AC and DC columns have different limits; do not transfer a value from one column to the other.
Low voltage • LV
In the lecture diagram, LV extends above the ELV boundary to 1,000 V AC or 1,500 V DC. A 230 V AC supply is therefore low voltage in this classification. “Low” does not mean safe to touch.
High voltage • HV
The HV region begins above 1,000 V AC or above 1,500 V DC in slide 10. Always identify the current type before choosing the category.
SELV is a protection system
SELV means safety extra-low voltage. Slide 10 marks 25 V AC / 60 V DC as its basic teaching values. Slide 27 refines these by contact and environment: protected-enclosure contact permits 50 / 120 V in usual or wet conditions. Do not turn 25 / 60 into a universal definition.
Read the SELV circuit
The lecture’s SELV diagram shows a transformer separating the supply from the extra-low-voltage output. Its secondary is not connected to the source PEN. The voltage limit is one part of the protective arrangement, not the whole arrangement.
In one line: 230 V mains is LV, not ELV.
Sources
Written by Ucenly. Based on the BEEZB / BEEZZ course materials:
- BEEZ_lecture_slides, p. 10, 27, 38
- bezpecnost_en, p. 48