UcenlyOpen in the app

Electrical Safety · BEEZB / BEEZZ · Topic 4 of 12

Current and the body

Magnitude, duration, frequency and path all matter.

Open the interactive lesson

Key ideas

Three thresholds, two scales

Slide 26: perception = 0.5 mA AC / 2 mA DC; pain = 3.5 mA AC / 10 mA DC; let-go = 5 mA AC / 25 mA DC. Let-go describes the current at which a person can still release a held electrode. These are teaching limits, not a prediction for every individual.

The body is not a fixed resistor

The model combines internal impedance Zi with skin impedances Zp1 and Zp2. Total impedance depends on touch voltage, so current versus voltage is nonlinear. Wet skin and wet contact surfaces lower impedance. Hand-to-hand and hand-to-foot paths are discussed in the book.

Ventricular fibrillation

Fibrillation of the ventricles prevents effective circulation and is identified as the main cause of electrical death. Its probability increases with current and duration. The vulnerable period corresponds to the ECG T-wave; the current path and the state of the heart also matter.

Frequency and time-current zones

The book describes AC as more dangerous than DC and 50–60 Hz as more dangerous than lower and higher frequencies. AC-1 usually gives no reaction; AC-2 usually no harmful effects; AC-3 usually means no organic damage is expected (it does not claim the absence of all effects); AC-4 adds fibrillation risk. Read current together with duration.

Charge is a different quantity

Slide 26 lists accumulated-charge thresholds of 0.5 µC for perception and 50 µC for pain; it gives no charge value for let-go. The book’s separate equipment table has different categories, including industrial equipment at 10 mA AC / 30 mA DC. Do not confuse that table with physiological let-go values.

In one line: DC thresholds are larger; 2 mA is not the AC perception value.

Sources

Written by Ucenly. Based on the BEEZB / BEEZZ course materials: