Electrical Safety · BEEZB / BEEZZ · Topic 7 of 12

Earthing systems

Follow PE, N and the fault path.

Open the interactive lesson

Key ideas

Decode TN, TT and IT

First letter: T = source directly earthed; I = source isolated from earth or connected through impedance. Second letter: N = exposed parts connected to the earthed source point; T = exposed parts have independent earth connection.

TN-S, TN-C and TN-C-S

TN-S keeps neutral N and protective PE separate throughout. TN-C combines their functions in PEN throughout. TN-C-S combines them in part of the system, then separates them.

PEN: fixed installation rules

In TN fixed installations, PEN requires at least 10 mm² copper or 16 mm² aluminium. After separation, N and PE must not be rejoined. Connect incoming PEN to the protective terminal. Extraneous conductive parts must not serve as PEN.

Czech TN-S socket

The slide shows a 230 V, 50 Hz socket: protective pin PE, L on the left and N on the right when viewed from the front in the illustrated orientation. Study the original wiring image.

Single-phase connections in the lecture

Slide 36 draws five single-phase connections: a) is marked FORBIDDEN; b) TN-C Class I, c) TN-C Class II, d) TN-S Class I and e) TN-S Class II are shown as permitted connections. This is the specific illustrated connection rule; the general class table also mentions installations with PE or PEN.

In one line: Separate means separate functions, not an absent neutral.