Electrical Safety · BEEZB / BEEZZ · Topic 6 of 12
Protection against shock
Combine protection, a fault path and timely disconnection.
Key ideas
Basic protection
Basic protection prevents contact with live parts in normal service: insulation, barriers and enclosures. The book requires at least IP2X for barriers/enclosures. Access requires a key/tool, disconnection with controlled restoration, or an appropriate intermediate barrier.
Obstacles and arm’s reach
Obstacles prevent unintentional contact, not deliberate access. Obstacles and placing out of reach are for areas restricted to skilled or instructed persons. Arm’s reach is the unaided reach from a standing/moving surface; parts more than 2.50 m apart are not treated as simultaneously accessible, with larger distances needed when long conductive objects are handled.
RCD: detect imbalance
An RCD compares currents in live conductors: the algebraic sum is zero normally; current escaping to earth creates an imbalance and trips the device. A sensitive RCD (typically IΔn 30 mA, the book’s example) is additional protection, not a replacement for basic protection. Residual-current detection alone is not overcurrent protection. It cannot protect a section using PEN.
Fault protection and bonding
Fault protection addresses exposed parts made live by failed insulation. Automatic disconnection can use a fuse, circuit breaker or RCD as appropriate. Main bonding joins protective/earthing conductors, PEN, metal pipework and structural metal at the building supply entry. Class II insulation and electrical separation are other protective methods.
Fault loop and the L curve
For TN protection, fault-loop impedance must be low enough for the protective device to disconnect within the required time: Zs × Ia ≤ U0. The L curve lies in AC zone 3, below zone 4 with a safety margin, and supports disconnection times as a function of prospective touch voltage.
In one line: An obstacle is not equivalent to a secured enclosure.
Sources
Written by Ucenly. Based on the BEEZB / BEEZZ course materials:
- BEEZ_lecture_slides, p. 39, 40, 41, 42
- bezpecnost_en, p. 17, 25, 30, 31