Electrical Safety · BEEZB / BEEZZ · Topic 5 of 12
Touch-voltage limits
Choose the right row before memorising a number.
Key ideas
Permanent touch voltage
Primary source, slide 28: in usual, wet or corrosion-aggressive conditions, permanent touch voltage is 25 V AC / 60 V DC. Very bad conditions, such as standing in water or a metal barrel, have dashes: no permanent value is given. For comparison, the textbook (Table 4.4.1) gives 50/120 V usual, 25/60 V wet and 12/25 V very bad.
Short-term fault voltage
Slide 28 gives short-term fault-condition touch voltages of 50 V AC / 120 V DC for usual, wet or corrosion-aggressive conditions. In very bad conditions the values are 12 V AC / 25 V DC. These belong to the short-term row.
SELV with accessible live parts
Slide 27 gives 25 V AC / 60 V DC when direct contact with live parts is possible in usual or wet conditions. For very bad conditions, the direct-contact row contains dashes.
SELV behind an enclosure
Where contact is only with the protective enclosure, slide 27 gives 50 V AC / 120 V DC in usual or wet conditions and 12 V AC / 25 V DC in very bad conditions. The enclosure condition is essential to the answer.
Lecture versus textbook
Use the lecture’s table for these questions. Book PDF p. 27 (printed p. 28) instead describes permanent limits as usual 50/120 V, wet 25/60 V, very bad 12/25 V. This conflicts with slide 28, which groups usual and wet at 25/60 V and gives no permanent very-bad-condition value. Both sources are shown; the lecture has priority for this study site. If a question names no source, know both tables.
In one line: A dash does not mean “use the short-term value indefinitely”.
Sources
Written by Ucenly. Based on the BEEZB / BEEZZ course materials:
- BEEZ_lecture_slides, p. 27, 28
- bezpecnost_en, p. 27